MDA Scientific System 16 Slave Module
MVI56-MDA16
The MVI56 MDA Scientific System 16 Gas Analyzer Slave Module allows Rockwell Automation ControlLogix processors to interface easily as a host with MDA Scientific CM4 gas monitoring hardware (See MVI56-MDA4 for a CM4 solution).
Features and Benefits
The MVI56-MDA16 module acts as an input/output module between the System 16 network and the Rockwell Automation backplane. The data transfer from the ControlLogix processor is asynchronous from the actions on the System 16 network. A 1600-word register space in the module is used to exchange data between the processor and the System 16 network.
General Specifications
- Single Slot - 1756 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
- Local or remote rack
Applications
This application is useful for any industry producing, using, or exposed to toxic or corrosive gases, where interfacing the System 16 Gas Analyzer with a ControlLogix processor is required.
Functional Specifications
- Support for the storage and transfer of up to 1600 registers to/from the ControlLogix processor's data files
- Two System 16 slave ports.
- Configurable parameters include:
- Baud Rate 110 to 115,200
- Parity None, Odd and Even
- Data Bits 5 to 8
- Stop Bits 1 or 2
- RTS On and Off Timing 0 to 65535 milliseconds
- Use of CTS Modem Line Yes or No
Operating Specifications
The MDA-16 product includes the following standard features:
- Two fully configurable serial ports, each capable of supporting the System 16 Slave functionality
- Supports one System 16 unit per serial port, 2 total per module
- Memory mapping will be pre-defined in the module to ease implementation in the ladder program
- RS-485 connection from each port directly to the System 16 unit
- Supported System 16 command codes:
- Write Commands
- 0x30 Sequential Sample Results
- 0x50 System Configuration
- 0x52 Point Enable Masks
- 0x53 Current System State
- 0x54 Point Configuration
- 0x56 Gas Table Data
- 0x61 Fault
- 0x68 Fault and Alarm Reset
- Operating Mode returned to ladder processor
- Error Codes returned to the ladder processor
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA @ 5 V
|
|
Operating Temperature
|
0 to 60° C (32 to 140° F)
|
|
Storage Temperature
|
-40 to 85° C (-40 to 185° F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Ordering Information
|
To order this product, please use the following:
|
MVI56-MDA16
|
MDA Scientific System 16 Gas Analyzer Slave Module
|
Note:
The MVI56-MDA16 is in a Final Sales Period of two years, effective October 14, 2008 until October 14, 2010. Thereafter, the product will continue to be supported until October 14, 2014. The recommended replacement for this product is MVI56-MDA4.
For more information on the Product Retirement Program, please visit: http://www.prosoft-technology.com/products/product_retirement_program
|
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|