PROFIBUS DP Master Network Interface Module for Quantum
PTQ-PDPMV1
The PROFIBUS DP Master Network Interface Module for Quantum is a powerful communication interface for Quantum platform processors. Developed under license from Schneider Electric, the module incorporates proprietary backplane technology that enables powerful data exchange with Quantum processors.
The PROFIBUS DP Master Network Interface Module for Quantum is designed according to IEC 61158 specifications and has been tested and certified according to PTO guidelines to guarantee proper interoperability on a PROFIBUS network. Acyclic parameter data can be transferred with Class 1 or Class 2 DP-V1 services, allowing processors to easily communicate with slave devices supporting PROFIBUS DP-V0 or DP-V1 protocol.
Features and Benefits
- The module is built on Siemens ASIC ASPC2 Step E with Infineon C165 Microprocessor.
- The firmware is flash-upgradable.
- The PROFIBUS DP Master Network Interface Module allows for slave messaging, diagnostics and alarm handling, and notification.
- Adheres to the Unity HEC Hot Standby Functional Specifications
- Cyclic Data: (Process I/O data) 1536 bytes of input and 1536 bytes of output data.
- Configure PTQ module and PROFIBUS network over Ethernet.
General Specifications
- Single Slot - Quantum backplane compatible
- The module is recognized as an Options module and has access to PLC memory for data transfer
- Configuration data is stored in non-volatile memory in the ProTalk module
- Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
- Up to six modules can be placed in a rack (up to four for Hot Standby implementations)
- Local rack - The module must be placed in the same rack as processor.
- Compatible with all common Quantum programming packages, including Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), and ProWORX (version 2.20 or later).
- Quantum data types supported: 3x, 4x
- High speed data transfer across backplane provides quick data update times.
- Sample ladder file available.
Applications
With the growing usage of the PROFIBUS DP-V1 protocol in the industrial marketplace, this product has a wide variety of application uses. Industries that use this technology include:
- Power and distribution applications
- Petrochemical
- Water and Gas Applications
- SCADA and DCS applications
- Manufacturing and Factory Automation Applications
Functional Specifications
- Easy-to-use drag and drop Busview configuration interface via ProSoft Configuration Builder software (see PSW-PCB Datasheet)
- Monitor/Modify of process data and DP-V1 acyclic data with online slave diagnostics
- Supports PROFIBUS PA slaves on the network through DP to PA link coupler
- Supports up to 125 slave devices with repeaters
- Supports extended diagnostic data (DP-V1 devices only)
- Supports all standardized baud rates, up to 12 Mbits/s
- Auto baud detection at all valid PROFIBUS DP-V1 rates
- Supports PROFIdrive 3.1 compliant parameter read and write operations
- Supports Sync and Freeze commands
- Alarm indications and confirmations handling (DP-V1 devices only)
- Supports Multicast and Broadcast telegrams (DP-V1 devices only)
- CRC checksum determination of slave configuration consistency to processor
- FDT/DTM PROFIBUS master transport communication DTM software included (see PSW-CDTM-PDPM)
Hot Standby
- Hot Standby features supporting the SE 140 671 CPU, using UnityPro.
- Supports up to four PTQ-PDPMV1 Hot Standby modules per rack.
- Diagnostic and status words are provided for Active Primary and Passive Secondary master health status.
- PROFIBUS switchover time will be nominal 100 ms not to exceed 300 ms.
- Cable break detection with segmented network slave quantity information.
- PROFIBUS health messages are generated from secondary master via FDL ping services.
- No setup parameters required. Module automatically detects Hot Standby system.
Physical
- PROFIBUS DP-V1 RS-485 interface with a 9-pin D shell female connector and isolated opto-couplers
- Master Status LED Indicators for Operations, Network Drop Communication, Master Token-Hold
Hardware Specifications
|
Operating Temperature
|
0 to 60° C (32 to 140° F)
|
|
Storage Temperature
|
-40 to 85° C (-40 to 185° F)
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
Vibration
|
Sine vibration 4 to100 Hz in each of the three orthogonal axes
|
|
Shock
|
30G, 11 mSec. in each of the three orthogonal axes
|
|
Dimensions (HxWxD), Approx.
|
250 x 103.85 x 40.34 mm 9.84 x 4.09 x 1.59 in
|
|
LED Indicators
|
Module Status
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status
Master Status Operations
Network Drop Communication
Master Token-Hold Master Database Configuration
|
|
Configuration Serial Port (PRT1)
|
DB-9M PC Compatible
RS-232 only No hardware handshaking
|
|
Configuration Ethernet Port
|
RJ45 Connector
Link and Activity LED Indicators Ethernet Broadcast Storm Resiliency less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
PROFIBUS Master Port
|
DB-9F Optically isloated RS-485 Ready, Run, Error, and Token LED Indicators
|
Ordering Information
| PTQ-PDPMV1 |
PROFIBUS DP Master Network Interface Module for Quantum |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|