ProSoft Technology, Inc.
Home > Products > for Rockwell Automation > Platform > CompactLogix > MVI69-MNET
Printable Page
 

Search | Clear


Modbus TCP/IP Interface Module

MVI69-MNET

The inRAx Modbus TCP/IP Communication Module is designed to allow CompactLogix processors to interface easily with other Modbus TCP/IP protocol-compatible devices.

Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other clients and server devices.

Features and Benefits

The MVI69-MNET module is a single slot solution that provides a powerful connection between Rockwell Automation's CompactLogix processor and Modbus TCP/IP network applications.

The TCP/IP Modbus network applications include those networks hosted by Modicon Quantum processors, networks controlled by operator interface software packages, and the growing number of manufactured devices that support this protocol. The module acts as an input/output module between the Modbus TCP/IP network and the Rockwell Automation backplane. The data transfer from the processor is asynchronous from the actions on the Modbus TCP/IP network. A 5000-word register space in the module exchanges data between the processor and the Modbus TCP/IP network.

With the growing trend of Ethernet technology in the industrial marketplace, this product has a wide variety of application uses.

  • Food processing
  • Petrochemical
  • Pulp and paper
  • Automobile manufacturing

Functional Specifications

General Protocol specifications

Type

Specifications

Communication parameters (configurable)

Port 1: Baud Rate: 110 to 57.6K baud

Floating Point Data

Floating point data movement supported, including configurable support for Enron implementation

Modbus Server Protocol Specifications

The server driver supports connections to Modbus TCP/IP clients supporting Service Port 502 using the standard MBAP protocol, and clients supporting Modbus on Service Port 2000.

Modbus Server Protocol Specifications

The server driver supports connections to Modbus TCP/IP clients supporting Service Port 502 using the standard MBAP protocol, and clients supporting Modbus on Service Port 2000.

General

Supports five independent server connections for Service Port 502

Supports five independent server connections for Service Port 2000

All data mapping begins at Modbus register 40001.

Status Data

Error codes, counters, and port status available

Modbus Function Codes

Code

Description

1:

Read Output Status

2:

Read Input Status

3:

Read Multiple Data Registers

4:

Read Input Registers

5:

Write Single Bit

6:

Write Single Data Register

15:

Write Multiple Bits

16:

Write Multiple Data Register

Modbus TCP/IP Client

The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.

One client connection available (connect up to 100 servers/devices with 100 commands)

Hardware Specifications

Dimensions

Standard 1769 Single-slot module

Current Load

800 mA max@ 5 VDC (Serial)
Power supply distance rating of 2 (L43 and L45 installations on first 2 slots of 1769 bus)

Operating Temp.

0 to 60 Deg C

 

32 to 140 Deg F

Storage Temp.

-40 to 85 Deg C

 

-40 to 185 Deg F

Relative Humidity

5 to 95% (w/o condensation)

LED Indicators

Power and Module Status

 

Application Status

 

CFG Port Activity

 

Error Status

CFG Port

RJ45 (DB-9M w/ supplied cable)

 

RS-232 only

 

No hardware handshaking

App Port (Ethernet)

10/100 MB Ethernet compatible interface

Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991

Shipped with Unit

RJ45 to DB-9M cables for each port

 

6-foot RS-232 configuration Cable

Ordering Information

MVI69-MNET Modbus TCP/IP Interface Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested