ProSoft Technology’s ILX34-MBS485 module is ideal to connect multiple devices up to 4,000 feet (1,219 meters) from your processor. These include SCADA and field device interface applications. The module can be used in CompactLogix L1 processors or Distributed 1734 Point I/O systems. In addition, the module can be configured as a Master or Slave.
Configuration Environment |
RSLogix 5000/Studio 5000 |
||
Communication parameters |
Baud Rate: 2400, 4800, 9600, 19200, 38400 |
||
Modbus Modes |
RTU mode (8-bit data size only) ASCII mode with LRC error checking |
||
Node Address |
1 to 247 |
||
Modbus Function Codes Supported |
1: Read Coil Status |
15: Force( Write) Multiple Coils |
Specification |
Description |
Power Supply |
10 to 28.8 VDC (Two 24V power supplies needed if using a Series A L16/L18 controller) |
Pointbus Current |
75mA @ 5 VDC |
Serial Line Voltages |
RS-232: -15 to +15 VDC RS-422/485: -7 to +12 VDC |
Number of Inputs |
1 Full duplex |
Module Location |
1734-TB or -TBS wiring base assembly (not included) 1734-TOP or -TOPS |
LED Indicators |
1 green/red module status indicator 1 green/red network status indicator 2 green TXD, RXD status indicators |
Operating Temperature |
32°F to +131°F (0°C to +55°C) |
Storage Temperature |
32°F to +131°F (0°C to +55°C) |
Relative Humidity |
5% to 95% RH with no condensation |
Dimensions (H x W x D) |
2.21 x 0.47 x 2.97 in 56 x 12 x 75.5 mm |
Shock |
30g peak acceleration (Operational) 50g peak acceleration (Non-operational) |
Vibration |
Tested 5g @ 10 to 500 Hz |
ESD immunity |
6kV contact discharges 8kV air discharges
|
CB Safety | 328.27 kB | Last Modified 08/07/2014 |
Declaration of Conformity (RoHS/CE) | 351.95 kB | Last Modified 12/18/2020 |
ATEX Letter of Conformity | 106.12 kB | Last Modified 05/12/2022 |
UL/cUL; Class 1, Div. 2 | 234.92 kB | Last Modified 04/08/2019 |
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1.92 MB | Last Modified 02/11/2022 |
Declaration of REACH Compliance | 339.85 kB | Last Modified 02/08/2021 |