The PS69 PROFIBUS DP Master module expands the functionality of ’s CompactLogix / MicroLogix family of processors to include PROFIBUS. This module supports both I/O control and messaging, thus integrating DPV0 and DPV1 functionality into CompactLogix / MicroLogix.
The PS69-DPM is a CompactLogix / MicroLogix compatible, PROFIBUS certified module, which enables controllers to communicate with a PROFIBUS network. The configuration and diagnostic of the PROFIBUS system is done via the serial diagnostic interface of the module using the System Configuration tool . The data exchange between controller and module is done via the I/O process data image using CompactLogix / MicroLogix backplane technology.
PROFIBUS certified |
Recognized quality certification mark |
FDT configuration software and communication DTM included |
Module DTM will configure master module and network slave devices. The DTM can be used in many FDT compatible software containers |
Sample ladder program |
Simplifies integration for quick and easy project start-up |
Supports CIP ladder logic messaging |
Request diagnostic, status and slave data based on ladder events. Offer better cyclic data performance |
The configuration and diagnostic of the PROFIBUS system is done via the serial diagnostic interface of the module using the PROSOFT.fdt system configuration software tool. PROSOFT.fdt is FDT style configuration software and a communication DTM is included with the module allowing easy configuration of the PROFIBUS Master and network slave devices.
The master and network configuration are stored in the FLASH memory of the module.
The PS69-DPM interface appears to the Logix Controller as a standard I/O module and can be configured with RSLogix™ 5000 by Rockwell Automation®.
Specification |
Description |
Slaves |
Maximum 125 |
Input/Output |
Maximum 244 Bytes per Slave |
Input Data |
Maximum 408 Bytes (*) |
Acyclic Data |
DPV1 |
Status data |
88 Bytes |
Output data |
Maximum 480 Bytes (*) |
Command data |
16 Bytes |
DPV1 services |
Read / Write class 1, Alarm |
Services |
Global-Control, Slave-Diag, Set-Parameter |
Sync, Freeze Command |
Supported |
Up to 32 PROFIBUS devices can be connected to one bus segment. If several bus segments are linked to each other with repeaters, there can be up to 127 devices on the network.
The maximum length of a bus segment depends on the baud rate used. Only PROFIBUS certified cable, preferably the cable type A, should be used.
Baud rate in kBit/s |
Max. Distance |
9.6 |
1,200 m / 4000 ft |
19.2 |
1,200 m / 4000 ft |
93.75 |
1,200 m / 4000 ft |
187.5 |
1,000 m / 3280 ft |
500 |
400 m / 1300 ft |
1,500 |
200 m / 650 ft |
3,000 |
100 m / 325 ft |
6,000 |
100 m / 325 ft |
12,000 |
100 m / 325 ft |
Parameter |
Value |
Impedance |
135 to 65 Ohm |
Capacity |
< 30 pF/m |
Loop resistance |
110 Ohm/km |
Wire gauge |
0.64 mm |
Specification |
Description |
Processor |
EC1-160P with integrated ASPC2 |
PROFIBUS Interface |
RS-485, max. 12 Mbps, potential free, according EN 50170 |
Diagnostic Interface |
RS-232, PS/2 Mini-DIN female connector, 9600 Baud, non isolated |
Power Supply |
260 mA at +5 V ±5 % |
Power Supply Distance Rating |
6 |
Dimensions |
Standard 1769 Single-slot module |
Burst |
EN 61000-4-4, 2 kV, 5 kHz |
Surge |
EN 61000-4-5, 2 kV common mode, 1 kV differential mode |
ESD |
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect |
Radiated/ Conducted Immunity |
EN 61000-4-3, 10 V/m, 30 to 1000 MHz, 80% AM, 1 kHz sinewave EN 61000-4-6, 10 V, 0.15 to 30 MHz |
Radiated/ Conducted Emission |
EN 55011 Class A |
Vibration/Shock |
IEC 600068-2-6, 10 to 150 Hz, IEC 600068-2-27, 15 g, 11 ms |
Operating Temp. |
32° F to 140° F (0° C to 60° C) |
Relative Humidity |
5% to 95% (without condensation) |
Agency Certification |
C-UL certified, UL 508 listed, CE |
PROFIBUS conformance |
PNO certified |
ATEX Letter of Conformity | 83.59 kB | Last Modified 05/12/2022 |
CB Safety | 347.28 kB | Last Modified 02/26/2020 |
CE Mark | 91.88 kB | Last Modified 02/22/2013 |
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1.92 MB | Last Modified 07/10/2020 |
UL/cUL; Class 1, Div 2 | 1.12 MB | Last Modified 02/27/2019 |
UL/cUL; Class 1, Div 2 (Canada) | 1.14 MB | Last Modified 02/27/2019 |
Declaration of Conformity | 440.44 kB | Last Modified 12/18/2020 |
Declaration of REACH Compliance | 340.56 kB | Last Modified 02/08/2021 |